| Topology |
True Online, Double Conversion VFI
|
| Construction |
Modular parallel hot-plugged modules, continuous operation
|
| INPUT |
| Voltage |
|
| Voltage Range |
|
| Current |
15A per phase for a single module, no inrush current at startup
|
| Frequency |
|
| Power Factor |
|
| THDI |
|
| OUTPUT
|
| Rated Power |
|
| Frequency Tracking Range |
|
| Frequency (in free-running mode) |
|
| Slew Rate |
|
| Voltage |
3 X 380/400V + N adjustable
|
| Static Regulation |
|
| Regulation for Unbalanced Load |
±1% for 100% unbalanced load
|
| Dynamic Response to 100% Load Step |
|
| Overload |
110% for 10 min; 125% for 60 sec; 1000% for 1 circle
|
| Waveform |
|
| THD |
Less than 2% for linear load
|
| Load CF (max) |
|
| AC-AC Efficiency (nominal) |
|
| DC-AC Efficiency (nominal) |
|
| BATTERIES
|
| DC-Link Voltage |
|
| Number of Batteries |
|
| GENERAL
|
| Maximum Power Dissipation (Po=8KW) |
333W (1136 BTU) for a single module
|
| Ambient Temperature |
-10° to +40° (opearting); -20° to +60° (storage)
|
| Relative Humidity |
|
| Altitude |
|
| Enclosure |
|
| Cooling |
Forced-multi-fan with speed control
|
| STANDARDS
|
| EMC Emission |
EN50091-2 Class A; IEC 62040-2
|
| EMC Imunity |
|
| Safety |
|
| Design |
EN50091-3; IEC62040-3 |
| Low Magnetic Field Radiation |
EMF as per ICNIRP |
| DIMENSION |
| 10kVA Modul (H x W x D) |
88mm (2U) x 483mm (19") x 455mm |
| Weight |
9kg |
| Matrix+ System (incl. STS & base modules) |
| Model |
10kVA |
20kVA |
30kVA |
40kVA |
50kVA |
60kVA |
70kVA |
80kVA |
90kVA |
100kVA |
| Dimension (cm) H |
69 |
79 |
88 |
97 |
107 |
116 |
126 |
135 |
144 |
154 |
W |
60 |
D |
69 |
| Weight (kg) |
98 |
113 |
128 |
143 |
158 |
173 |
188 |
203 |
218 |
233 |
ACCOUSIC NOISE (@1.5m from front of unit) |
| Noise (dBA) half load |
48 |
52 |
53 |
54 |
55 |
55.8 |
56.4 |
57 |
57.5 |
58 |
| Noise (dBA) full load |
51 |
54 |
55 |
57 |
58 |
58.8 |
59.4 |
60 |
60.5 |
61 |