Input |
Capacity (VA) |
800 |
Voltage (W) |
220, 230, 240 +/-25% at line input |
Frequency (Hz) |
50 or 60Hz, +/-10% (auto sensing) |
Output |
| Voltage (on battery) |
Simulated sine wave 220V, 230V, 240V, +/-5% |
| Frequency (on battery) |
50 or 60Hz +/- 1% |
| Transfer Time |
2/4 milisecond, including detection time |
| Auto Voltage Regulation (AVR) |
AVR automatically increase output voltage 15% above input
voltage if = 9% to -25% of nominal. AVR decrease output
voltage 13% below input voltage if +9% to +25% of nominal |
Protection & Filtering |
| Spike Protection |
480 Joules, 2ms |
| Unit Input |
Fuse for overload & short circuit protection |
| Overload Protection |
Automatic power off if overload exceeds 110% o nominal at 60 second and 130% at 3 seconds |
| Short Circuit |
Immediate termination of UPS power output |
Battery |
| Type |
Sealed, maintenance-free lead acid batteries with 3-6 years typical life time |
| Typical Recharge Time |
10 hours (to 90% of full capacity) |
| Protection |
Auto discharge protection |
Physical |
| Weight (kg) |
6kg |
| Dimension (w x d x h) |
85 x 330 x 140mm |
Environment |
| Ambient Operation |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0 - 40° C |
| Operation Noise |
<40dBA (1 meter from surface) |