  Home > Products > Off-Line UPS > X800
     
 
download
 
 
Input
Capacity (VA)
800
Voltage (W)
220, 230, 240 +/-25% at line input
Frequency (Hz)
50 or 60Hz, +/-10% (auto sensing)
Output
Voltage (on battery)
Simulated sine wave 220V, 230V, 240V, +/-5%
Frequency (on battery)
50 or 60Hz +/- 1%
Transfer Time
2/4 milisecond, including detection time
Auto Voltage Regulation (AVR)
AVR automatically increase output voltage 15% above input
voltage if = 9% to -25% of nominal. AVR decrease output
voltage 13% below input voltage if +9% to +25% of nominal
Protection & Filtering
Spike Protection
480 Joules, 2ms
Unit Input
Fuse for overload & short circuit protection
Overload Protection
Automatic power off if overload exceeds 110% o nominal at 60 second and 130% at 3 seconds
Short Circuit
Immediate termination of UPS power output
Battery
Type
Sealed, maintenance-free lead acid batteries with 3-6 years typical life time
Typical Recharge Time
10 hours (to 90% of full capacity)
Protection
Auto discharge protection
Physical
Weight (kg)
6kg
Dimension (w x d x h)
85 x 330 x 140mm
Environment
Ambient Operation
3,500 meters max. elevation, 0-95% humidity non-condensing, 0 - 40° C
Operation Noise
<40dBA (1 meter from surface)

 

 
All Rights Reserved. Copyright 2011 Contronetix (M) Bhd.